PQube®

Power Standards Lab

Gonzel's Machine Shop PQube #2 - Gonsel's Machine Shop #2

Oakland, California machine shop
(near Oakland Raiders Coliseum)

Refresh
 
Meters

Meter Value
L1-L2
L2-L3
L3-L1
L1 Amp
L2 Amp
L3 Amp
Frequency
Voltage THD 2.4%
Current TDD 3.5%
RMS Flicker Pinst 0.1
Pst 0.4
Plt 0.3
Voltage THD 2.4%
Current TDD 3.5%
TH1 Probe 2
 
Energy

Meter Value
Power 22.29kW
Apparent Power 25.54kVA
Reactive Power 12.45kVAR
True Power Factor 0.87
Energy
(since 2009/04/09)
1.301MWh
Apparent Energy
(since 2009/04/09)
1.320MVAh
Carbon
(since 2009/04/09)
245.7kg
Carbon Rate 7.23kg/h
Peak RMS Current
(since 2009/04/09)
1-cycle 327.4Arms
1-minute 110.4Arms
15-minute 98.1Arms
Peak Power
(since 2009/04/09)
1-cycle 94.28kW
1-minute 34.10kW
15-minute 29.43kW
Peak Apparent Power
(since 2009/04/09)
1-cycle 94.28kVA
1-minute 34.10kVA
15-minute 29.43kVA
 
Internal Sensors

Meter Value
Battery voltage 4.22V
Battery current 0.01A
Battery cycles
(since 2009/04/09)
10
CPU temperature 62 deg C
 

Data from the PSL PQube® by www.PowerStandards.com